City Government > City Departments > Utilities > Wastewater System Maintenance

Utilities
Wastewater System Maintenance


ItemMaintenance
Influent Lift Station 5 flight pumps 40 hp (annual oil change)
RAS Lift Station 2 flight pumps 30 hp (annual oil change)
WAS Lift Station 2 flight pumps 5 hp (annual oil change)
North and South Final Clarifiers 2 flight scum pump 5 hp (annual oil change)
Non-Potable Pumps American Marsh, 2 turbine pumps 20 hp, grease stuffing box weekly, grease pump motor every 6 months
Headwork’s Stair screen and Wash press Vulcan Industries Lubricate all shaft bearings monthly and Check gear box for oil add or change every 6 months. Lubricate motor every 6 months.
Hydro Grit Separator /turn table Lubricate every week.
Classifier Cyclone oil change every 6 months and grease every 3 months.
Grit pump grease motor every 6 months.
North and South Aeration Basin 2 aerators Eimco Water Technologies Reducer housing oil change every year. Grease motor every year.
Reducer lower bearing grease every 6 months.
North and South Final Clarifiers Eimco Water Technologies Turn table oil change every year, grease motor every year
Digester Blowers 3 blowers grease motors every 9 months / clean filters every 3 months
Belt Press, Conveyor Belt, Moyno Sludge pumps and Polymer pumps Grease belt press every 6 months, grease conveyor belt every 6 months.
Change Gear box oil every year on belt press and lubricate motors every year.
2 Moyno sludge pumps grease motor every year.
2 Polymer pumps, clean ancillary water and or polymer strainers as needed, flush system weekly (no lubrication required).
Gaffey Electric Chain Hoists Influent Lift Station Load chain clean and coat the SAE 90 gear oil every 6 months.
Gearing change oil every year.
Gaffey Electric Chain Hoists RAS/WAS Lift Station Load chain clean and coat the SAE 90 gear oil every 6 months.
Gearing change oil every year.
Air Compressor Ultraviolet Disinfection System Annual maintenance oil change, change air filter every 6 months.
Air Compressor Non-potable water system Annual maintenance oil change, change air filter every 6 months.
Plant Generator Routine checks on oil, coolant, run times and fuel levels.
Front Gate Grease gear and chain every two months.
Air Conditioning Control room Aeration, WAS/ RAS Building Change filters every two to three months.
Air Conditioning Control Room Operations Office Change filters every two to three months.
Ultraviolet Disinfection System Clean Sleeves, Channel and effluent weir every two weeks.